Inductive Combined Transformer EJGF

Type EJGF combined transformers are used in high-voltage substations within the 245-550 kV range. They transfer high voltage and high current into standardised, equivalent values for meters, measuring and protection devices.

SF6-Insulated Inductive Combined Transformer EJGF, Instrument Transformer

The voltage transformer component is located in the top of the pressure-resistant head housing and the current transformer cores at the bottom. In the current transformer unit, the iron core is set to high-voltage potential and the secondary windings to earth potential. The current transformer cores are fitted in a protective core shell made of massive cast aluminium, which is connected short-circuit proof to the bushing. The secondary outlets are passed through the SF6 /air bushing in the connection terminal box on the base support of the insulator.

The current distribution along the insulator is optimised by a special layout of the control electrode inside the silicone composite insulator.

The housing components consist of helium-tight, corrosion-resistant cast aluminium. All housing components under pressure are individually typetested according to applicable pressure vessel standards.

The SF6 gas density is monitored by a temperature-compensated gas density monitor with alarm contacts. The special design means the function of the gas density monitor can be checked without dismounting it.

A corrosion-resistant metal rupture disc, protected by a metal cover, located at the top of the head housing ensures safe pressure relief in case of error. The generously designed terminal box is equipped with a cover that opens sidewards.

Pure SF6 gas is used for ambient temperatures up to -40°C. The transformer is filled with a mixed gas for lower ambient temperatures up to -60°C.

Find your local contact
SF6-Insulated Inductive Combined Transformer EJGF, mounted in Substation, Instrument Transformer

Features

  • Reduced transport costs with one unit instead of two
  • Less space needed with just one footprint
  • Lower material costs due to a reduced number of supports and fewer primary connections
  • Lower installation effort as only one unit has to be installed instead of two

Highlights

Easy primary changeover

  • A clear and easy primary changeover with a ratio of 1:2 or 1:2:4 is available.
  • The primary changeover is adjusted with one metal plate at one side of the head only.
  • No need to dismount or move the primary connections during adjustment.

Excellent protection against moisture

  • The inner side of the instrument transformer is protected against moisture by means of special sealing rings.
  • All housings are designed with a drainage area to protect the sealing surfaces of the housings against rain. This significantly reduces gap corrosion.
  • The housing elements are connected with special stainless steel screws. They are designed in such a way that no humidity can enter the screw hole.

Installation-friendly terminal box

  • The generously sized terminal box with a cover that can be opened sidewards, is secured with captive screws. It can accommodate terminal blocks, fuses, spark gaps and sealable covers.
  • By default, all terminal boxes have a flange without holes. Cable glands can be preinstalled on request.

Specifications and Downloads

Technical Specifications

Dimensions

SF6-Insulated Inductive Combined Transformer EJGF, Outline drawing, Instrument Transformer

Technical data

Type EJGF

 

245

300

330

362

420

550

Standard   IEC / IEEE
Highest voltage for equipment kV 245 300 300 363 420 550
Rated power-frequency withstand voltage kV 460 460 460 575 630 680
Rated lightning impulse withstand voltage kV 1050 1050 1175 1175 1425 1550
Frequency Hz 50 / 60
Primary rated current A ≤ 5000
Secondary rated current A 1 / 5
Rated short-time thermal current [Ith] kA / 3s ≤ 80
Rated dynamic current [Idyn] kA ≤ 200
Accuracy class CT part   0.1-3; P; PR; PX; TPS; TPX; TPY; TPZ
Accuracy class VT part   0.1-3; 3P; 6P
Rated thermal limiting output VT part VA ≤ 3000
Max. simultaneous burden (cl. 0.2) VA 300
Max. number of CT cores   8
Max. number of VT windings   5
Nominal operating / transport overpressure (20°C)   4 / 0.5

Type EJGF

 

 

245

300

330

362

420

550

Height of unit* A mm 4980 4980 6140 6140 6500 7440
Height to primary terminal* B mm 3375 3375 4730 4730 5090 5890
Depth of unit including terminal box

C

mm

845 845 1088 1088 1088 1088
Depth of unit base

D

mm

749 749 1088 1088 1088 1088
Width of unit base

E

mm

736 736 1075 1075 1075 1075
Distance between screw holes at base

F

mm

600 600 900 900 900 900
Min. creepage distance*

 

mm

6700 7500 8250 9050 10500 13750
Gross weight approx.*

 

kg

940 940 1000 1000 1600 1700
Gas weight, approx. *   kg 45 45 58 58 60 63

 

*with standard composite silicone insulator, creepage distance 25 mm/kV

Back to overview

Related Products

Inductive Current Transformer JGF

  • SF6-gas insulated
  • Primary winding changeover
  • Pressure release by using a metal burst-disc
  • Only silicone insulator available

Inductive Voltage Transformer EGF

  • SF6-gas insulated
  • Pressure release by using a metal burst-disc
  • Gas density control
  • Only silicone insulator available

Inductive Combined Transformer EJOF

  • Oil-paper insulated
  • Guaranteed accuracy over entire service life
  • Explosion-tested casing
  • Fine-graded bushing
  • Low space requirements for installation