Busbar system | GASLINK®
- Modular and compact desing
- Protection against electrical shock hazards
- Self-recombinating gas insulation
- No aging effects on insulating material
MGC Moser-Glaser has developed a totally enclosed medium voltage SF6 gas insulated busbar system for connections between GIS - switchgears and between GIS and transformers.
The copper conductors are centered with special high voltage epoxy insulators inside the outer aluminum protection tubes. A separate control panel allows an accurate pressure control of the GASLINK® busbar system. The excellent sealing between the compartments guarantee a maximum leakage rate of no more than 0,5% per year.
High quality DURESCA® bushings are being used for the connections to transformers, coils, capacitors and other apparatus.
Specifications and Downloads
Technical Specifications
- Rated voltage: up to 40,5 kV
- Rated current: up to 3150 A
- Rated thermal short time current: 40 kA / 3 sec
- Rated operating pressure: 0,15 MPa / 0,25 MPa absolute
- Max. leakage rate per year: less than 0,5 %
- Min. phase distance: 200 mm
Features
- protection against electrical shock hazards
- self-recombinating gas insulation
- no aging effects on insulating material
- no additional fire protection needed