DDX 9121b

The DDX 9121b is a fully digital state-of-the-art high-performance PD (partial discharge) and RIV (radio interference/influence voltage) detector.

DDX9121b - Modular Partial Discharge (PD) & Radio Interference Voltage (RIV) Detector

The DDX 9121b is modular and fits a wide range of PD detection applications. 1 to 9 simultaneous and 4 to 36 non-simultaneous measuring inputs are possible. Traditional partial discharge measurements according to the latest IEC 60270 or RIV measurement, PD under DC and PD cable site location (SL) are covered. Pass/Fail test or Phase Resolved PD (PRPD) analysis are possible as well.

1 to 9 stackable unit(s) communicate with a remote software, which handles data acquisition and display of PD information, test results and generates reports. 

The DDX 9121b increases the laboratory sensitivity as it is equipped with digital filters allowing the measurement frequency band to be shifted into a less noisy range and suppressing frequency dependent noise. In addition, there are gating (windowing) possibilities to blank out static interferences.

The reports can be printed out or displayed as a web page (XML format). Users can also export results to a CSV file. Software also provides screenshots function for inclusion in other reports.

Find your local contact

Features

  • User defined measuring band
  • Unique combination of analog and high order digital filters
  • High resolution spectrum analyzer with oscilloscope
  • Modular design, 1 to 9 detectors
  • Easily upgradable
  • Embedded switch with four PD inputs per detector (optional)
  • PRPD (Phase Resolved Partial Discharge) pattern (fingerprinting)
  • Derived IEC quantities (average discharge current, repetition rate)
  • Data acquisition and test report generation
  • PD Site Location (SL) on power cables
  • Unique “trigger on charge Q” feature
  • AC and DC measuring modes
  • Simultaneous RIV (NEMA or CISPR) and PD reading

Specifications and Downloads

Images

Back to overview

Related Products

9230 Series

Standardized HV Capacitor Series for Partial Discharge or AC Measurement

9230/25/1-PD

Coupling Capacitor 25 kV for Partial Discharge Measurement

9230/30/9-PD

Coupling Capacitor 30 kV for Partial Discharge Measurement

AKV 9310

Measuring impedance for partial discharge measurement optimized for DDX 9121b

AKV 9330

Active Measuring Impedance Optimized for PD Testing of Large Power Capacitors

KAL 9510

Intermediate Partial Discharge Calibrator

KAL 9511

Basic Partial Discharge Calibrator  

KAL 9520

Advanced Reference Partial Discharge Calibrator

KAL 9531

RIV (NEMA and CISPR) Calibrator